  • online UPS 6~10kVA
    Basic Features

    ● Miniaturization design

    The ultimate small body and heat dissipation structure design, smaller volume, lighter weight, better heat dissipation, more reliable products.

    ● Online type design, zero conversion

    Digital-X series UPS adopts dual-conversion online design, intelligent MCU / DSP precision control; when mains is interrupted or restored, UPS realizes zero time switching between city mode and battery mode, effectively ensuring the reliability of load operation.

    ● High-quality sine-wave output

    High quality sinusoidal waves (THD<3%, linear) can be output either in mains mode or battery mode to provide the best power supply for the load.

    ● Energy-efficient

    The PFC power factor correction design and IGBT transformation technology are adopted, and the input power factor is 20.99, and the whole machine efficiency is 90%.

    ● Detection and self-protection function

    Digital-X series UPS can simulate the power failure and enter the battery mode. This function can be executed at any time through "self-test button" on the panel, or with random monitoring software; perfect self-protection function, peak current and short circuit protection design, super load impact resistance.

    ●TVSS function

    Namely, TRANSIENT VOLTAGE SURGE SUPPRESS burst wave voltage protection function. For conversion protection, including FAX, TELEPHONE, MODEM network, etc.

    ● DC startup function

    In the mains power outage condition, if UPS is needed to start the computer or other load equipment, Digital-X series UPS can be directly turned up in battery mode, making the use of UPS more convenient and reliable.

    ● Automatic bypass / manual bypass / maintenance bypass (optional)

    In addition to the automatic bypass function, Digital-X series UPS also has the function of manually setting the bypass on the panel keys; when necessary, the manual maintenance bypass is optional for online maintenance.

    ● Optional lightning protection function

    Optional D class lightning protection device, with surge prevention, lightning protection design, effectively protect the equipment from lightning interference.

    ● EPO emergency shutdown function (optional)

    Optional EPO switch to realize emergency shutdown of UPS.

    ● Rich and humanized LCD / LED content display

    UPS operating status (mains mode / battery mode / bypass mode), input and output, battery power, load size, and failure code, etc., at a glance.

    ● Long-term type power supply design

    The Digital-X series UPS offers all long-acting machines for users to choose from. The appropriate battery pack can bring the discharge time of the UPS to about 8 hours to meet the requirements of different power grid environments. Digital-X series UPS long-acting machine extends the discharge time and the battery re-charging machine is also very strong, which can provide an initial charging current of about 3 ~ 4A (which can also be selected according to user needs).

    ● Can be used with a generator

    The ultra-wide input voltage and frequency range enable Digital-X series UPS to be used together with mainstream brand generators to extend the use time, while effectively removing the impure power generated by the generator and providing safe and stable power supply for the load.

    ● Can be connected to the perceptual load

    Digital-X series UPS for inductive load.

    ● Random monitoring software

    Rs 232 communication interface (optional USB interface), random monitoring software, to realize the intelligent management of UPS by users.

    ● Equipped with Intelligent Slot intelligent slot for remote monitoring (optional)

    The Digital-X series UPS is equipped with- -a Intelligent SIot smart slot, the users can choose the SNMP network card, to realize the centralized monitoring and remote monitoring and other functions.

    Technical Specifications
    Model item 1K 1KS 2K 2KS 3K 3KS 6K 6KS 10K 10KS
    Rated power 1000VA/900W 2000VA/1800W 3000VA/2700W 6kVA/5.4kW 10kVA/9kW
    AC Input Input system Single phase (L/N+PE)

     
    Nominal voltage HV: 208/220/230/240Vac
    LV:100/110/120/127Vac

     
    Frequency 50/60Hz

     
    Voltage   range HV: 110~285VAC±5VAC
    LV: 55-145Vac±3VAC

     
    Frequency range 40~70)±0.5Hz

     
    Input power factor >0.99

     
    Bypass Voltage Range  HV: 180~265VAC×(1±3%)
    LV: 80~140VAC×(1±3%)


    Battery
    Input
    Nominal Voltage 24V 24V/36V
    customizable
    48V 48V/72V 72V 72V/96V 144/192V 192V 192V/240V

     
    Battery Capacity & Quantity 12V/7AH
    x 2pcs
    External 12V/7AH
    x 4pcs
    External 12V/7AH
    x 6pcs
    External 12V/7AH  x 12/16pcs External 12V/7AH
    x16/20pcs
    External

     
    Backup Time Half loaded8minutes,
    Full loaded ≥3minutes(standard)
    Half loaded6minutes,
    Full loaded ≥3minutes(standard)

     
    Battery charger time Charger to 90% battery capacity in 5 hours(standard) Dependent on the capacity of external batteries (long backup time)



    AC Output
    Output wiring system Single phase (L/N+PE)

     
    Inverter Mode
    Output voltage
    HV:200V/208/220/230/240Vac±2%
    LV:100/110/120/127Vac±2%

     
    Waveform Sine Wave 

     
    Harmonic Distortion THD<2% (linear load)
    THD<7% (nonlinear load)

     
    Output frequency 50/60±4Hz (Sync mode)
    50/60H1% (Fix Freq. mode)

     
    Overload capability 105125%≥ 60s,126150%≥30s   The recover point is 70%

     
    Transfer time Battery <-> Line  Mode :0ms
    Efficiency Line Mode HV:86%
    LV:86%
    HV:88%
    LV:86%
    HV:89%
    LV:87%
    HV:92%
    LV:88%
    HV:93%
    LV:89%

     
    Battery Mode HV&LV:85% HV&LV:86% HV&LV:87%
     

     
    Communications RS232 RS485(optional), Dry contact(optional), Network Card(Option)
    Alarm Function AC/DC input under abnormal, overload condition and Inverter problems
    Protection Function AC input or output above or below the range of voltage, overload, over temperature and short circuit protection
    Noise <50dB <55dB
     

    remarks:

    1. Select the rated capacity (output power) PF = 0.8.

    2. The model with "S" is a extended time model, and the battery should be configured according to the external battery DC voltage according to the endurance time, and the DC voltage of D 2 KS-X external battery can be selected as 96 Vdc.

    3. Other internal battery configurations are available in the following models:

    D1K-X: 12V7Ah/9Ah*3 ; D2K-X: 12V7Ah/9Ah*6.

    4. Load in high altitude = rated power *reduction coefficient

    altitude(m)

    1000

    1500

    2000

    2500

    3000

    3500

    4000

    4500

    5000

    Frequency reduction coefficient

    100%

    95%

    91%

    86%

    82%

    78%

    74%

    70%

    67%

     If the UPS is used above 1000m, the decreasing rated output must be used, as shown in the table above.

    * The above parameters may be adjusted and changed, please refer to the physical object.

     