Hi, welcome to visit our website      Home / Sitemap / Contact

 

  • Rack/tower high frequency online UPS 6 ~ 10kVA
    Basic Features

    1. 19'rack design to provide more flexible and reliable power protection for critical equipment.

    2. Real online design, output pure sine wave, pollution-free, conversion time is zero.

    3. Intelligent MCU / DSP design, using PFC power factor correction, the input power factor is greater than 0.99, the whole machine efficiency is more than 93%, and the input current harmonic is less than 5%.

    4. Using high frequency and IGBT transformation technology, improve the efficiency and reliability of the whole machine, small volume, light weight.

    5. Perfect self-protection function, peak current and short circuit protection design, super load load impact resistance.

    6. Optional D class lightning protection device with surge prevention, lightning protection design, effectively protect the equipment from lightning interference.

    7. 6 ~ 20 KVA can choose the parallel redundancy function to realize the N + 1 parallel redundancy.

    8. Intelligent local and remote monitoring function RS232 interface, compatible with SNMP.

    9. Tower and rack design, tower type and frame type free combination, more convenient installation.

     

    Technical Specifications
    Model item 1KR 1KRS 2KR 2KRS 3KR 3KRS 6KRS 10KRS
    Rated power 1000VA/900W 2000VA/1800W 3000VA/2700W 6kVA/5.4kW 10kVA/9kW
    AC Input Input system Single phase (L/N+PE)
      Nominal voltage HV: 208/220/230/240Vac
    LV:100/110/120/127Vac
      Frequency 50/60Hz
      Voltage   range HV:110~285VAC±5VAC
    LV: 55-145Vac±3VAC
      Frequency range 40~70)±0.5Hz
      Input power factor >0.99
      Bypass Voltage Range  HV: 180~265VA(3%)
    LV: 80~140VAC×(3%)


    Battery
    Input
    Nominal Voltage 24V 24V/36V 48V 48V/72V 72V 72V/96V 192V/240V
      Battery Capacity & Quantity 12V/7AH
    x 2pcs
    External 12V/7AH
    x 4pcs
    External 12V/7AH
    x 6pcs
    External External
      Backup Time Half loaded6minutes,
    Full loaded ≥2minutes(standard)
     Dependent on the capacity of external batteries
      Battery charger time Charger to 90% battery capacity in 5 hours(standard)
     Dependent on the capacity of external batteries (long backup time)



    AC Output
    Output wiring system Single phase (L/N+PE)
      Inverter Mode
    Output voltage
    HV:200V/208/220/230/240Vac±2%
    LV:100/110/120/127Vac±2%
      Waveform Sine Wave 
      Harmonic Distortion THD<2% (linear load)
    THD<7% (nonlinear load)
      Output frequency 50/60±4Hz (Sync mode)
    50/60H1% (Fix Freq. mode)
      Overload capability 105125%≥ 60s,126150%≥30s   The recover point is 70%
      Transfer time Battery <-> Line  Mode :0ms
    Efficiency Line Mode HV:86%
    LV:86%
    HV:88%
    LV:86%
    HV:89%
    LV:87%
    HV:92%
    LV:88%
    HV:93%
    LV:89%
      Battery Mode HV&LV:85% HV&LV:86% HV&LV:87%    
    Communications RS232 RS485(optional), Dry contact(optional), Network Card(Option)
    Alarm Function AC/DC input under abnormal, overload condition and Inverter problems
    Protection Function AC input or output above or below the range of voltage, overload, over temperature and short circuit protection
    Noise <50dB <55dB
Some of the images and text on this site are from the internet. If there are any copyright issues, please notify us so we can handle them.
Website maintain
  • Hotline
    86-18033431559
  • wechat